• nýbjtp

CJ-C40 1,5kv 275V 40ka 4p rafmagnsbylgjuvarnartæki SPD

Stutt lýsing:

Smíði og eiginleiki

  • Notkunarstaður: Undirdreifingarráð
  • Verndarmáti: LN, N-PE
  • Bylgjumat: In = 20kA(8/20μs)
  • IEC/EN/UL Flokkur: Class II / Type 2 / Type 1CA
  • Hlífðarþættir: High Energy MOV
  • Hús: Stengjanleg hönnun
  • Samræmi: IEC 61643-11:2011 / EN 61643-11:2012

Upplýsingar um vöru

Vörumerki

Tæknilegar upplýsingar

IEC rafmagns 150 275 320 385 440
Nafnspenna (50/60Hz) 120V 230V 230V 230V 400V
Hámarks samfelld rekstrarspenna (AC) (LN) Uc 150V 275V 320V 385V 440V
(N-PE) Uc 255V
Nafnútstreymisstraumur (8/20μs) (LN)/(N-PE) In 20kV/20kA
Hámarks losunarstraumur (8/20μs) (LN)/(N-PE) Imax 40kA/40kA
Spennuverndarstig (LN)/(N-PE) Up 1,0kV/1,5kV 1,5kV/1,5kV 1,6kV/1,5kV 1,8kV/1,5kV 2,0kV/1,5kV
Fylgdu núverandi truflunareinkunn (N-PE) Ef ég 100 ARMS
Viðbragðstími (LN)/(N-PE) tA <25ns/<100ns
Varaöryggi (hámark) 125A gL/gG
Skammhlaupsstraumeinkunn (AC) (LN) ISCCR 20kA / 50kA
TOV Standast 5s (LN) UT 180V 335V 335V 335V 580V
TOV 120 mín (LN) UT 230V 440V 440V 440V 765V
ham Standast Örugg mistök Örugg mistök Örugg mistök Örugg mistök
TOV þola 200ms (N-PE) UT 1200V
Rekstrarhitasvið -40ºF til +158ºF[-40ºC til +70ºC]
Leyfilegur raki í notkun Ta 5%…95%
Loftþrýstingur og hæð RH 80k Pa..106k Pa/-500m..2000m
Terminal skrúfa tog Mmax 39,9 lbf-in[4,5 Nm]
Þversnið leiðara (hámark) 2 AWG (fast, strandað) / 4 AWG (sveigjanlegt)
35 mm2 (fast, strandað) / 25 mm2 (sveigjanlegt)
Uppsetning 35 mm DIN tein, EN 60715
Verndargráða IP 20 (innbyggt)
Húsnæðisefni Hitaplast: Slökkvistig UL 94 V-0
Hitavörn
Rekstrarástand / villuvísun Grænt í lagi / Rauður galli
Fjartengiliðir (RC) / RC skiptigeta Valfrjálst
Þversnið RC leiðara (hámark) AC: 250V/0.5A; DC: 250V/0.1A; 125V/0.2A;75V/0.5A
16 AWG (fast) / 1,5 mm2 (fast)

 

Yfirspennuvarnarbúnaður (2)


  • Fyrri:
  • Næst:

  • Skrifaðu skilaboðin þín hér og sendu okkur