IEC rafmagns | 150 | 275 | 320 | 385 | 440 | ||
Nafnspenna (50/60Hz) | 120V | 230V | 230V | 230V | 400V | ||
Hámarks samfelld rekstrarspenna (AC) | (LN) | Uc | 150V | 275V | 320V | 385V | 440V |
(N-PE) | Uc | 255V | |||||
Nafnútstreymisstraumur (8/20μs) | (LN)/(N-PE) | In | 20kV/20kA | ||||
Hámarks losunarstraumur (8/20μs) | (LN)/(N-PE) | Imax | 40kA/40kA | ||||
Spennuverndarstig | (LN)/(N-PE) | Up | 1,0kV/1,5kV | 1,5kV/1,5kV | 1,6kV/1,5kV | 1,8kV/1,5kV | 2,0kV/1,5kV |
Fylgdu núverandi truflunareinkunn | (N-PE) | Ef ég | 100 ARMS | ||||
Viðbragðstími | (LN)/(N-PE) | tA | <25ns/<100ns | ||||
Varaöryggi (hámark) | 125A gL/gG | ||||||
Skammhlaupsstraumeinkunn (AC) | (LN) | ISCCR | 20kA / 50kA | ||||
TOV Standast 5s | (LN) | UT | 180V | 335V | 335V | 335V | 580V |
TOV 120 mín | (LN) | UT | 230V | 440V | 440V | 440V | 765V |
ham | Standast | Örugg mistök | Örugg mistök | Örugg mistök | Örugg mistök | ||
TOV þola 200ms | (N-PE) | UT | 1200V | ||||
Rekstrarhitasvið | -40ºF til +158ºF[-40ºC til +70ºC] | ||||||
Leyfilegur raki í notkun | Ta | 5%…95% | |||||
Loftþrýstingur og hæð | RH | 80k Pa..106k Pa/-500m..2000m | |||||
Terminal skrúfa tog | Mmax | 39,9 lbf-in[4,5 Nm] | |||||
Þversnið leiðara (hámark) | 2 AWG (fast, strandað) / 4 AWG (sveigjanlegt) | ||||||
35 mm2 (fast, strandað) / 25 mm2 (sveigjanlegt) | |||||||
Uppsetning | 35 mm DIN tein, EN 60715 | ||||||
Verndargráða | IP 20 (innbyggt) | ||||||
Húsnæðisefni | Hitaplast: Slökkvistig UL 94 V-0 | ||||||
Hitavörn | Já | ||||||
Rekstrarástand / villuvísun | Grænt í lagi / Rauður galli | ||||||
Fjartengiliðir (RC) / RC skiptigeta | Valfrjálst | ||||||
Þversnið RC leiðara (hámark) | AC: 250V/0.5A; DC: 250V/0.1A; 125V/0.2A;75V/0.5A | ||||||
16 AWG (fast) / 1,5 mm2 (fast) |