IEC rafmagns | 75 | 150 | 275 | 320 | ||
Nafnspenna (50/60Hz) | Uc/Un | 60V | 120V | 230V | 230V | |
Hámarks samfelld rekstrarspenna (AC) | (LN) | Uc | 75V | 150V | 270V | 320V |
(N-PE) | Uc | 255V | ||||
Nafnútstreymisstraumur (8/20μs) | (LN)/(N-PE) | In | 20 kA/25kA | |||
Hámarks losunarstraumur (8/20μs) | (LN)/(N-PE) | Imax | 50 kA/50 kA | |||
Hvatafhleðslustraumur (10/350μs) | (LN)/(N-PE) | Iimp | 12,5kA/25kA | |||
Sérstök orka | (LN)/(N-PE) | W/R | 39 kJ/Ω / 156 kJ/Ω | |||
Hleðsla | (LN)/(N-PE) | Q | 6,25 As/12,5As | |||
Spennuverndarstig | (LN)/(N-PE) | Up | 0,7kV/1,5 kV | 1,0kV/1,5 kV | 1,5 kV/1,5 kV | 1. 6kV/1,5 kV |
(N-PE) | Ef ég | 100 ARMAR | ||||
Viðbragðstími | (LN)/(N-PE) | tA | <25 ns/<100 ns | |||
Varaöryggi (hámark) | 315A/250A gG | |||||
Skammhlaupsstraumeinkunn (AC) | (LN) | ISCCR | 25kA/50kA | |||
TOV Standast 5s | (LN) | UT | 114V | 180V | 335V | 335V |
TOV 120 mín | (LN) | UT | 114V | 230V | 440V | 440V |
ham | Standast | Örugg mistök | Örugg mistök | Örugg mistök | ||
TOV þola 200ms | (N-PE) | UT | 1200V | |||
UL rafmagns | ||||||
Hámarks samfelld rekstrarspenna (AC) | MCOV | 75V/255V | 150V/255V | 275V/255V | 320V/255V | |
Spennuverndareinkunn | VPR | 330V/1200V | 600V/1200V | 900V/1200V | 1200V/1200V | |
Nafnútstreymisstraumur (8/20μs) | In | 20kA/20kA | 20kA/20kA | 20kA/20kA | 20kA/20kA | |
Skammhlaupsstraumeinkunn (AC) | SCCR | 100kA | 200kA | 150kA | 150kA |